CVE-2026-45452
8.3HighPublished 15 Oct 2026 · NVD status: Deferred · AI triage by gemini-3.8-flash
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- Low
- User interaction
- None
- Impact
- High impact on confidentiality, integrity
- Weakness
- CWE-134
Impact
Authenticated network attackers can execute arbitrary code, alter system state, or crash affected PLC controllers. They only need low-privilege network access to the target device.
Root cause
An externally controlled format string vulnerability allows user-supplied input to alter process memory.
Affected systems
Unitronics UniStream Pro (B10 / C10) using UniLogic versions prior to 1.41.329
CVSS v3.1 · CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L
Fix & remediation
Upgrade UniLogic to version 1.41.329 or later and reflash the UniStream Pro controllers. If patching must wait, isolate the controllers onto a restricted OT VLAN and block untrusted network access to their management ports.
AI-suggested. Run it in staging first and check it against the vendor advisory. Why?
NVD description
Use of Externally-Controlled format string vulnerability in Unitronics Unitronics UniStream Pro/UniLogic. This issue affects Unitronics UniStream Pro/UniLogic: Unitronics UniStream Pro versions only (B10 / C10) – UniLogic versions prior to 1.41.329.