Ad · Leaderboard 728×90

CVE-2026-45451

8.3High

Published 15 Oct 2026 · NVD status: Deferred · AI triage by gemini-3.8-flash

8.3High
Attack vector
Network
Complexity
Low
Privileges needed
Low
User interaction
None
Impact
High impact on confidentiality, integrity
Weakness
CWE-287

Impact

Authenticated network attackers can bypass authentication controls to read and modify sensitive data or compromise PLC operations. They need low-privilege network access to the device.

Root cause

Improper authentication logic in the UniLogic management software allows validation bypass.

Affected systems

Unitronics UniStream Pro (B10 / C10) running UniLogic versions prior to 1.41.329

CVSS v3.1 · CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L

Fix & remediation

Upgrade UniLogic to version 1.41.329 or later and re-flash the affected UniStream Pro PLC. If updating immediately is not possible, restrict network access to the PLC interface via firewall rules or isolate it on an out-of-band management VLAN.

AI-suggested. Run it in staging first and check it against the vendor advisory. Why?

Ad · In-content banner

NVD description

: Improper Authentication vulnerability in Unitronics Unitronics UniStream Pro/UniLogic. This issue affects Unitronics UniStream Pro/UniLogic: Unitronics UniStream Pro versions only (B10 / C10) – UniLogic versions prior to 1.41.329.